Liquid Cooling Package LCP Inline CW
Liquid Cooling Package LCP Inline CW
Bayed climate control designed for siting within a bayed enclosure suite. The hot air is extracted at the rear of the unit, cooled and then expelled forwards to the cold aisle.
3312530
/ H: 2000mm (78.74")
W: 300mm (11.81")
D: 1200mm (47.24")
$0.00
Dimensions | 300 mm (12 ") |
---|---|
Temperature range | +15°C |
Dimensions | 1200 mm (48 ") |
Benefits | By using high water inlet temperatures the proportion of indirect free cooling is increased which in turn reduces operating costs Fan modules configurable as n+1 redundancy. Maximum energy efficiency due to EC fan technology and IT-based control Minimal pressure loss at the air end which in turn minimizes the power consumption of the fans Optimum adaptability due to dynamic continuous control of the cold water volume flow Targeted cooling output thanks to modular fan units The separation of cooling and enclosure prevents water from entering the server enclosure Redundant temperature sensor integrated at the air end Ideal for use in conjunction with a heat pump as the LCP CW glycol versions generate high return water temperatures Improved heat recovery through high water return temperatures when using LCP CW glycol versions Optimum access for maintenance and service from the front and the rear Standard 3-phase connection for electrical redundancy Tool-free fan module replacement Up to 53 kW cooling output on a footprint of just 0.36 m² |
Rated operating voltage | 230V 1~ 50Hz/60Hz 400V |
Temperature control | 2-way control ball valve Infinitely variable fan control |
Cooling medium | Water |
Type of connection (electrical) | Connector |
Duty cycle | 100 % |
Water connections | DN 40 (G 1½" external thread) |
Packaging unit | 1 pc(s). |
Weight/packaging unit | 260 kg (573.2 lb.) |
EAN | 4028177811652 |
Customs tariff number | 84158300 |
IT Monitoring | Direct connection of the unit via SNMP over Ethernet Integration into RiZone Monitoring of all system-relevant parameters such as server air intake temperature server waste air temperature water inlet/return temperature water flow cooling output fan speed leakage. |
ETIM 6.0 | EC002515 |
Variant | Row Cooling |
ETIM 5.0 | EC002515 |
eCl@ss 8.0/8.1 | 27180712 |
Total cooling output | 30 kW |
eCl@ss 7.0/7.1 | 27180712 |
EC fan | yes |
eCl@ss 6.0/6.1 | 27180712 |
eCl@ss 5.1/5.1.4 | 27180712 |
Note | Water quality according to unit specifications. |
Product description (long) | SK LCP Inline Protruding R15 CW 30 kW RAL 7035 WHD: 300x2000x1200 mm |
Total cooling output/number of fan modules required | 10kW / 1 20kW / 2 30kW / 3 |
Fans may be exchanged with the system operational | yes |
Installation in bayed enclosure | Protruded |
Color | RAL 7035 |
Dimensions | 2000 mm (79 ") |
Function principle | The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product a raised floor is not necessary |
Options | Direct connection of additional CMC III sensors is also possible Racks 2200 mm high |
Protection category IP to IEC 60 529 | IP 20 |
Number of fan modules in supplied state | 1 |
Air throughput unimpeded air flow | 4800 m³/h (2825.2 cfm) |
Declarations | Declaration of conformity |
---|
Download
(high resolution)
(high resolution)

Pos. | Name | Shop | Valid From | Model No. |
---|---|---|---|---|
1 | CMC III Processing Units | - | 7030000 | |
2 | Water control module for LCP | - | 3398196 | |
3 | Control module fan for LCP | - | 3398197 | |
4 | Fan module For LCP rack/Inline, CW | - | 3312016 | |
4 | Radial fan | - | 3396746 | |
10 | Power pack | - | 3396752 | |
90 | Ball valve | - | 3396689 | |
100 | Leakage sensor | - | 3396748 | |
130 | Temperature sensor | - | 3396692 | |
170 | Temperature sensor | - | 3396750 | |
180 | Temperature sensor | - | 3396751 |