InRow LCP Chilled Water, H 2000mm W 300mm D 1200mm, up to 30kw

InRow LCP Chilled Water, H 2000mm W 300mm D 1200mm, up to 30kw

Chilled water InRow cooling up to 30kW. Protruding fans direct the airflow sideways for efficient and effective air flow delivered direct to the equipment.

3311538 / H: 2000mm (78.74") W: 300mm (11.81") D: 1200mm (47.24")

$100.00
Function principleThe hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product a raised floor is not necessary
IT MonitoringDirect connection of the unit via SNMP over Ethernet
Integration into RiZone
Monitoring of all system-relevant parameters such as server air intake temperature server waste air temperature water inlet/return temperature water flow cooling output fan speed leakage.
ColorEnclosure frame and interior: RAL 7035
Exterior: RAL 9005
Protection category IP to IEC 60 529IP 20
OptionsVarious sensors
Racks
VariantRow Cooling
Supply IncludesIncl. 1 fan module.
Total cooling output to DIN EN 14511:Total cooling output to DIN EN 14511: 10 kW (34121 BTU)
20 kW (68242 BTU)
30 kW (102364 BTU)
L 22 L 30: 30 kW (102364 BTU)
L 22 L 45: 30 kW (102364 BTU)
Total cooling output/number of fan modules required10kW / 1
20kW / 2
30kW / 3
Total cooling output to DIN EN 1451130 kW
Air throughput2825 cfm (3 fans)
Rated operating voltage230V 1~ 50Hz/60Hz
208V 2~ 60Hz
DimensionsHeight: 2000 mm (79 ")
Width: 300 mm (12 ")
Depth: 1200 mm (48 ")
Temperature control2-way control ball valve
Infinitely variable fan control
Installation in bayed enclosureProtruded
Temperature range+15°C
Cooling mediumWater
Note10/20/30 kW
Type of connection (electrical)Connector
EC fanyes
Fans may be exchanged with the system operationalyes
Water connectionsDN 40 (G 1½" external thread)
Number of fans2
3
1
Packaging unit1 pc(s).
Weight/packaging unit200 kg (440.9 lb.)
EAN87740
More Info
Approvals
Data sheets
Product data sheet
Technical data sheet
Documentation
Instructions