Liquid Cooling Package LCP Inline DX

Liquid Cooling Package LCP Inline DX

Ideal for cooling small and medium-sized IT applications.

3311480 / H: 2000mm (78.74") W: 600mm (23.62") D: 1200mm (47.24")

$100.00
DimensionsWidth: 600 mm (24 ")
Depth: 1200 mm (47 ")
BenefitsMaximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end which in turn minimizes the power consumption of the fans
Redundant temperature sensor integrated at the air end
Due to the speed-regulated compressor the cooling output adapts to the actual requirements
Special maintenance of the LCP DX due to separation of cooling and server enclosures
Operating costs can be saved through the use of indirect free cooling
Temperature monitoring and control.
ApplicationsIdeal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
NoteVariant with UL approval available on request
Rated operating voltage400V 3~ 50Hz
380V - 480V 3~ 60Hz
Cooling mediumWater/glycol
Type of connection (electrical)Connection clamp
Duty cycle100 %
Miniature circuit-breaker/fuse40 A
Packaging unit1 pc(s).
Weight/packaging unit398 kg (877.4 lb.)
EAN4028177691384
Customs tariff number84158200
IT MonitoringDirect connection of the unit via SNMP over Ethernet
Integration into RiZone
ETIM 6.0EC002515
VariantRow Cooling
ETIM 5.0EC002515
eCl@ss 8.0/8.127180712
Total cooling output35 kW
eCl@ss 7.0/7.127180712
EC fanyes
eCl@ss 6.0/6.127180712
eCl@ss 5.1/5.1.427180712
Device modulates without interruption in the cooling output range between8kW - 35kW
Total cooling output/number of fan modules required
35kW / 3
VersionLCP Inline DX/FC
Fans may be exchanged with the system operationalyes
Installation in bayed enclosureFlush
Dimensions2000 mm (79 ")
Function principleAbsorbed thermal energy is emitted to the ambient air at the external condenser location without heating up the installation room
LCP for use within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device cooled by the high-capacity compact impellers and blown back into the room or cold aisle after cooling
The LCP DX/FC versions contain both refrigerant as well as a water/glycol heat exchanger. A free cooler is also integrated in the external condenser.
OptionsAir filter
Condensate lift pump
Higher cooling output
Humidifier
Low-temperature/high-temperature condenser (-40°C/+53°C)
Reheater
Rated Current (Max)31.6 A
Refrigerant cooling mediumR410a
Temperature range+15°C...+35°C
Air throughput unimpeded air flow9900 m³/h (5826.9 cfm)
More Info
Data sheets
Safety data sheet
Documentation
Instructions
Pos. Name Shop Valid From Model No.
1 Compressor
- 3398452
2 Speed Control
- 3398453
6 Pump
- 3398562
10 Radial fan
- 3398454
20 Expansion valve
- 3398455
25 Dryer
- 3398456
30 Pressostat
- 3398324
31 Pressure transmitter
- 3398188
32 Pressure transmitter
- 3398186
40 Controller
- 3398457
41 Power pack
- 3398459
45 Fault signaling module
- 3398097
55 Display
- 3398094
70 Temperature sensor
- 3397682
71 Temperature sensor
- 3397682
72 Temperature sensor
- 3397682
73 Temperature sensor
- 3398185
74 Temperature sensor
- 3398561