InRow LCP Direct Expansion, H 2000mm W 300mm D 1000mm, up to 12kw

InRow LCP Direct Expansion, H 2000mm W 300mm D 1000mm, up to 12kw

InRow Direct Expansion cooling up to 12kW. Fans direct the airflow forward into the cold aisle.

3311435 / H: 2000mm (78.74") W: 300mm (11.81") D: 1000mm (39.37")

$0.00
Function principleThe LCP draws in the air at the sides at the rear of the server enclosures cools it using high-performance compact impellers and blows the cooled air back into the front part of the server enclosure at the sides
ColorRAL9005
Protection category IP to IEC 60 529IP 20
NoteEthernet cable 2482.720 required with SNMP network card 3311.320
VariantRow Cooling
Total cooling output to DIN EN 14511:12 kW (40945 BTU)
Device modulates without interruption in the cooling output range between3kW - 12kW
Total cooling output/number of fan modules required
12kW
Number of fan modules in supplied state4
Total cooling output to DIN EN 14511Total cooling output: 12 kW
L 35 L 35: 12 kW
L 35 L 45: 8 kW (27297 BTU)
Air throughput (unimpeded air flow)4800 m³/h (2825.2 cfm)
Rated operating voltage208V 1~ 60Hz
DimensionsHeight: 2000 mm (79 ")
Width: 300 mm (12 ")
Depth: 1000 mm (39 ")
Temperature controlInfinitely variable fan control
Inverter-controlled compressor
Installation in bayed enclosureFlush
Temperature rangeStorage: -20°C...+60°C
Ambient temperature range: +15°C...+35°C
Cooling mediumR410a
Type of connection (electrical)Connection clamp
EC fanyes
Fans may be exchanged with the system operationalyes
Packaging unit1 pc(s).
Weight/packaging unit201 kg (443.1 lb.)
Customs tariff number84158300
More Info
Approvals
UL + C-UL
Data sheets
Graphics
Product data sheet
Safety data sheet
Technical data sheet
Documentation
Instructions