InRow LCP Chilled Water, H 2000mm W 300mm D 1200mm, up to 30kw closed loop system

InRow LCP Chilled Water, H 2000mm W 300mm D 1200mm, up to 30kw closed loop system

Chilled water InRow cooling up to 30kW. The closed loop cooling design captures the cold air and hot at the source with a solid front and rear door creating a built in cold aisle, hot aisle configuration. The fans direct the airflow sideways for efficient and effective air flow delivered direct to the equipment. Available with solid front and rear doors or any combination of the two for a hybrid design.

3311238 / H: 2000mm (78.74") W: 300mm (11.81") D: 1200mm (47.24")

$100.00
Function principleThe LCP draws in the air at the sides at the rear of the server enclosures cools it using high-performance compact impellers and blows the cooled air back into the front part of the server enclosure at the sides
IT MonitoringDirect connection of the unit via SNMP over Ethernet
Integration into RiZone
Monitoring of all system-relevant parameters such as server air intake temperature server waste air temperature water inlet/return temperature water flow cooling output fan speed leakage.
ColorEnclosure frame and interior: RAL 7035
Exterior: RAL 9005
Protection category IP to IEC 60 529IP 20
OptionsVarious sensors
VariantRack cooling
Total cooling output to DIN EN 14511:Total cooling output to DIN EN 14511: 10 kW (34121 BTU)
20 kW (68242 BTU)
30 kW (102364 BTU)
L 22 L 30: 30 kW (102364 BTU)
L 22 L 45: 30 kW (102364 BTU)
Total cooling output/number of fan modules required10kW / 1
20kW / 2
30kW / 3
Total cooling output to DIN EN 1451130 kW
Rated operating voltageRated operating voltage: 230V 1~ 50Hz/60Hz
208V 2~ 60Hz
Note: 208 V
DimensionsHeight: 2000 mm (79 ")
Width: 300 mm (12 ")
Depth: 1200 mm (48 ")
Temperature control2-way control ball valve
Infinitely variable fan control
Installation in bayed enclosureFlush
Temperature range+15°C
Cooling mediumWater
Type of connection (electrical)Connector
EC fanyes
Fans may be exchanged with the system operationalyes
Water connectionsDN 40 (G 1½" external thread)
Number of fans2
3
1
Packaging unit1 pc(s).
Weight/packaging unit200 kg (440.9 lb.)
EAN87738