TopTherm Blue e Wall-Mounted Cooling Units, NEMA 4X Total cooling output 0.50 – 2.50 kW

TopTherm Blue e Wall-Mounted Cooling Units, NEMA 4X Total cooling output 0.50 – 2.50 kW

Energy-efficient Blue e wall-mounted cooling units in power categories 500 W to 2,500 W with e-Comfort controller integrated as standard, RiNano coating on the condenser and electrical condensate evaporation. Protection category NEMA 4X.

3303504 / H: 620mm (24.41") W: 285mm (11.22") D: 298mm (11.73")

$100.00
Total cooling output to DIN EN 14511L 35 L 35 at 50 Hz: 0.55 kW (1876 BTU)
L 35 L 35 at 60 Hz: 0.66 kW (2252 BTU)
L 35 L 50 at 50 Hz: 0.33 kW (1126 BTU)
L 35 L 50 at 60 Hz: 0.4 kW (1364 BTU)
Air throughput (unimpeded air flow)External circuit: 315 m³/h (185.4 cfm)
Internal circuit: 265 m³/h (156 cfm)
Rated operating voltage230V 1~ 50Hz/60Hz
Rated current (max)At 50 Hz: 2.6 A
At 60 Hz: 2.6 A
Start-up current (max)At 50 Hz: 5.1 A
At 60 Hz: 6.4 A
Miniature circuit-breaker/fuse10A
MaterialStainless steel 1.4404 (AISI316L)
Temperature rangeAmbient temperature range: +10°C...+55°C
Setting range: +20°C...+50°C
DimensionsHeight: 620 mm (24 ")
Width: 285 mm (11 ")
Depth: 298 mm (12 ")
Protection category IP to IEC 60 529Internal circuit IP 55
External circuit IP 34
Protection category NEMA:NEMA 4X
Rated Power PelL 35 L 35 at 50 Hz: 0.39 kW
L 35 L 35 at 60 Hz: 0.41 kW
L 35 L 50 at 50 Hz: 0.42 kW
L 35 L 50 at 60 Hz: 0.39 kW
Energy efficiency ratio (EER) 50 Hz L35 L35 to DIN EN 145111.4
Temperature controle-Comfort Controller (factory setting +35°C)
Weight/packaging unit25 kg (55.1 lb.)
Refrigerant-cooling mediumRefrigerant: R134a
Quantity: 170 g (6 oz)
Global Warming Potential (GWP): 1430
CO₂ equivalent (CO₂e): 0.24 t
Supply includesDrilling template
Fasteners
Nano-coated condenser
Wired ready for connection (plug-in terminal strip)
Integral electric condensate evaporation
Note3303.XXX without integral condensate evaporation
Note on Model No.without integral condensate evaporation
Packaging unit1 pc(s).
EAN4028177384255
Customs tariff number84158200
Product description (long)SK cooling unit Blue e wall-mounted NEMA 4X 0.55 kW 230 V 1~ 50/60 Hz Stainless steel WHD: 285 x 620 x 298 mm
More Info
Approvals
CSA
UL + C-UL - FTTA
UR + C-UR
Certificates
EAC
Declarations
Declaration of conformity
Declaration of conformity - F-gas regulation

Drawings

Format Dimension Drawing Filename  
Open CAD drawing in new tab
Data sheets
Documentation
Info sheet
Safety instructions
White paper
Specialist literature
The Rittal technology library
EPLAN Data Portal
Pos. Name Shop Valid From Model No.
1 Compressor
- 3397497
5 Radial fan
- 3396248
10 Radial fan
- 3396265
20 Expansion valve
- 3397602
25 Dryer
- 3397522
30 Pressostat
- 3397603
40 Controller
- 3396665
55 Display
- 3396668
70 Temperature sensor Blue
- 3397533
71 Temperature sensor Red
- 3397536
72 Temperature sensor Yellow
- 3397540
73 Temperature sensor White
- 3397618
90 Evaporator
- 3397709
100 Condensers
- 3397590
102 Display cable