Computer Room Air Conditioner CRAC DX

Computer Room Air Conditioner CRAC DX

Precision climate control unit for direct evaporation with external air-cooled condenser

3300397 / H: 1980mm (77.95") W: 2155mm (84.84") D: 860mm (33.86")

$100.00
Number of compressors2
Dimensions2155 mm (85 ")
in empty space (5 m distance)58.7 dB(A)
Power consumption, total12 kW
Rated current (max.)22.3 A
Refrigerant cooling medium18.4 kg (40.6 lb.)
Air volume11310 m³/h (6656.8 cfm)
External compression50 Pa (50 Pa)
max.17000 m³/h
Cooling output, total44.8 kW (152863 BTU)
Dimensions860 mm (34 ")
Cooling output, sensible41 kW (139897 BTU)
in empty space (5 m distance)58.7 dB(A)
Power consumption, total12 kW
VersionCondenser unit with axial fan
Rated current (max.)22.3 A
DescriptionThe precision climate control unit for direct evaporation CRAC DX draws warm waste air from the top of your data center cools it in a closed heat exchanger and blows the cooled filtered supply air into the raised floor with overpressure. From there the air is returned to the data center via ventilation panels. The connection to the air-cooled condenser is via refrigerant lines. The condenser unit is positioned externally.
Supply includesBasic unit and external condenser unit
NoteA neutral conductor is required
NoteA neutral conductor is required
Note on Model No.Article can be configured options available
CRAC DX U S 048.P2.H6
Rated operating voltage400V 3~ 50Hz
Start-up current (max.)116 A
NoteNet weight refers to the basic unit without options
Packaging unit1 pc(s).
Weight/packaging unit591 kg (1302.9 lb.)
EAN4028177702226
Customs tariff number84158200
Product description (long)SK Computer Room Air Conditioner CRAC DX 44 8 kW 400 V 3~ 50 Hz WHD: 2155x1980x860 mm
Rated current (max.)30 A
Total cooling output/number of fan modules required2
Rated power Pel1.08 kW
Number of cooling circuits1
Filter class to DIN EN 779G4
in operating status175 kg
ColorSheet metal parts: RAL 7015
Substructure and frame: RAL9005
Dimensions1980 mm (78 ")
OptionsCondensate lift pump
Reheater
Base frame
Serial interface BACnet Ethernet SNMP TCP/IP
Steam humidifier
EC fan
Inverter-controlled compressor
Rated Current (Max)5.7 A
Refrigerant cooling mediumR410a
Number of fans2
Number of fans (max.)2
Air volume11310 m³/h (6656.8 cfm)
More Info